Wrong numbers, no fault: three Siemens SCL math traps and how to avoid them

A shift total goes negative and the CPU never faults. Here's why SCL integer math overflows silently, how typed constants change the result, when Real stops adding, and a small LAD and SCL example that does it right.

Math that's wrong without a fault

A shift total on the HMI reads -20,536 kg. The CPU is in Run, there's no fault, and nothing is flashing. The code multiplies a part count by a part weight, both stored as Int, and the answer was too big for an Int. In Siemens SCL, math like this can give a wrong answer with no fault and no warning, so you have to design the data types up front.

Three traps and how to avoid them

  • The result type comes from the operands, not from where you store it. SCL picks the data type of an expression from its operands: two Int values give an Int result, and mixing Int and DInt gives DInt.1 Storing the answer in a DInt doesn't help if the multiply already overflowed. Convert an operand first (INT_TO_DINT, or CONV in LAD).
  • Typed constants set the math type. INT#1 is a constant with a fixed type; plain 1 is untyped. Mixing a typed constant with a big untyped one can force the whole expression into the smaller type, so INT#1 + 50000 is calculated as an Int and comes out as -15,535. Siemens recommends not mixing typed and untyped constants in one expression.2 Type both constants, or neither.
  • Real runs out of digits. A 32-bit Real holds about 7 significant digits. A flow total that keeps adding small amounts slows down and eventually stops changing. Use LReal on CPUs that support it, or keep totals as integers in a sensible unit and convert only for display. (Our run-hours tutorial shows the same problem on the Rockwell side.)

The part total, done right

One small example: a shift's total kilograms from a part count and a part weight, both Int because that's how the scale sends them. The fix is to widen both to DInt before the multiply.

Ladder

Three LAD networks: convert, convert, multiply, using the Siemens CONV and MUL boxes (parameters IN/OUT and IN1/IN2/OUT). This is a schematic drawing of the networks, not a TIA Portal screenshot; numbering starts at 0 here, while TIA calls them Network 1 to 3.

Schematic only, drawn in our usual ladder style with Siemens instruction names. In TIA Portal LAD each box also has EN/ENO pins and you pick the data type on the box. None of these are Rockwell instructions.

On a phone, swipe sideways to see the whole rung.

Widen the part count to DInt before multiplying0CONVConvert (Int to DInt)IN#PartCount0 ←OUT#PartCount_D0 ←
Widen the part weight too1CONVConvert (Int to DInt)IN#PartWeight_kg0 ←OUT#PartWeight_D0 ←
Multiply in DInt: 300 x 150 = 45,000 fits (an Int stops at 32,767)2MULMultiply (DInt)IN1#PartCount_D0 ←IN2#PartWeight_D0 ←OUT#ShiftKg0 ←
(End)

SCL

The same multiply in SCL, with the two other traps from this page shown as comments and code. Siemens SCL is its version of IEC 61131-3 structured text.

// Temp/static: #PartCount, #PartWeight_kg : Int
//              #ShiftKg : DInt;  #TotalLiters : LReal
// Trap 1: Int * Int is calculated as Int, then stored.
//   300 * 150 = 45000 does not fit in Int (max 32767).
#ShiftKg := #PartCount * #PartWeight_kg;                       // WRONG

// Fix: widen one operand first so the math runs in DInt.
#ShiftKg := INT_TO_DINT(#PartCount) * INT_TO_DINT(#PartWeight_kg);   // OK

// Trap 2: a typed constant sets the data type of the math.
#ShiftKg := INT#1 + 50000;        // WRONG: done in Int, gives -15535
// Don't mix typed and untyped constants. Type both, or neither:
#ShiftKg := INT#1 + DINT#50000;   // OK: done in DInt
#ShiftKg := 1 + 50000;            // OK: untyped, widest type on the CPU

// Trap 3: a Real total that stops adding.
//   Real holds about 7 significant digits. Above 16,777,216
//   adding 1.0 does nothing. Use LReal (S7-1500) for totals.
#TotalLiters := #TotalLiters + #FlowThisScan;                // LReal

Overflow in SCL doesn't stop the CPU. Unless you turn on the block property "Set ENO automatically", SCL doesn't report it through ENO either; it just stores a wrong number.3

Educational example. This code has not been compiled, downloaded, or tested on a controller. It is not production-ready or drop-in code. Treat it as a starting point to review, adapt, and test on your own system. It is standard control logic, not safety logic.

Habits that prevent this

  • Size tags for the worst case, not today's numbers. A count that's never over 300 today can be 3,000 after a line speed change.
  • Turn on "Set ENO automatically" for blocks where a math error must be caught, and check ENO. It adds some run-time overhead, so use it where it matters.3
  • Test the edges. In a simulator, force the inputs to their maximum values and see what the math does before it goes live.
  • Check conversions. Converting a large DInt to Int, or a Real to an integer, can fail or round. Look at the conversion rules for your CPU family.4

Sources

  1. Siemens, STEP 7 (TIA Portal) help, "Arithmetic expressions" (data type of the result): docs.tia.siemens.cloud.
  2. Siemens, STEP 7 help, "Calculating with constants in SCL" (typed and untyped constants): docs.tia.siemens.cloud.
  3. Siemens, STEP 7 help, "Enabling and disabling the property 'Set ENO automatically' in SCL": docs.tia.siemens.cloud.
  4. Siemens, STEP 7 help, "Overview of data type conversion (S7-1500, S7-1200 G2)": docs.tia.siemens.cloud.

Instruction details were checked against the vendor documentation linked above. Behavior can change between software and firmware versions, so check the help for the version you run.